Understanding conductor sizing, insulation, and termination temperatures is crucial for electrical safety and code compliance. These topics are frequently tested on NEC electrical exams because they directly impact the performance and longevity of electrical systems. Proper conductor sizing ensures that wires can handle the intended current without overheating, while correct insulation and termination temperatures prevent degradation and potential fire hazards.
Example Conductor Sizing, Insulation & Termination Temperature Questions on NEC Electrical Exams
A 500 kcmil THHN copper conductor is terminated on a 75°C rated circuit breaker. The maximum allowable ampacity of this conductor is ________ amperes.
The ampacity of a size 4 AWG THW copper conductor, when installed in a conduit with three other current-carrying conductors of the same size and insulation, and in a location with an ambient temperature of 98°F, is ________ amperes.
When a cable is run in free air with four cables per phase and one end terminates on a 75°C circuit breaker, the minimum size of single aluminum XHHW-2 conductor that can be used to feed a 2000 A, 600 V, 3Ø MCC is ________ kcmil.
How to Identify a Conductor Sizing, Insulation & Termination Temperature Question on NEC Electrical Exams
Key phrases to look out for in these types of questions:
- Ampacity
- Conductor size (AWG or kcmil)
- Insulation type (THW, XHHW, THHN, etc.)
- Ambient temperature
- Number of current-carrying conductors
- Installation method (conduit, free air, etc.)
- Termination temperature rating
When you spot these elements:
- Confirm it's a conductor sizing, insulation, or termination temperature question
- Refer to NEC sections 310.15 / 16 / 17 and associated tables
How to Solve Conductor Sizing, Insulation & Termination Temperatures Questions
- Determine Conductor Temperature Rating:
- Refer to NEC 110.14 for guidance
- Consider termination temperature limitations
- Identify Installation Method:
- Single conductor in free air: Use Table 310.17
- Conductor in raceway, cable, or directly buried: Use Table 310.16
- Apply Temperature Correction Factors:
- Use if ambient temperature exceeds 30°C (86°F)
- Refer to Table 310.15(B)(1)
- Apply Adjustment Factors:
- Use if more than three current-carrying conductors are present
- Refer to Table 310.15(C)(1)
Interpretation of Rules for Conductor Temperature & Termination Temperature from NEC 110.14(C)(1)(a) & (b)
Lowest Equipment Temperature Rule:
- Use the lowest temperature rating of any connected equipment in the circuit.
- Example: If a circuit has a 60°C-rated disconnect, a 75°C-rated motor, a 75°C-rated breaker, and 75°C-rated XHHW conductor, you must size the conductor based on the 60°C column (lowest equipment temperature in the circuit).
- If equipment termination temperatures are not listed, do not use the conductor's rated temperature and use the ampacity based / wire size rule.
Ampacity-Based / Wire Size Rule:
- For circuits 100 A or less or marked for 14 AWG through 1 AWG conductors: Use the 60°C column for conductor sizing.
- For circuits over 100 A or marked for 2 AWG conductors and above: Use the 75°C column for conductor sizing.
Let's do some example questions:
Q: When selecting XHHW wire to carry 32 amps, what temperature column should I use in Table 310.16 of the NEC?
A: 60°C column as termination temperature is not listed.
Q: When selecting XHHW wire to carry 32 amps and terminating on a 60°C/75°C circuit breaker, what temperature column should I use in Table 310.16 of the NEC?
A: 75°C column as termination temperature allows for 75°C.
Q: When selecting XHHW wire to carry 32 amps in a motor circuit with a 60°C rated controller and terminating on a 60°C/75°C circuit breaker, what temperature column should I use in Table 310.16 of the NEC?
A: 60°C column as it's the lowest termination temperature in the circuit (motor controller).
Q: When selecting ZW-2 wire to carry 32 amps in a motor circuit with a 90°C rated controller and terminating on a circuit breaker, what temperature column should I use in Table 310.16 of the NEC?
A: 60°C column as the circuit breaker termination temperature is not listed and the circuit is below 100A.
Conductor Sizing, Insulation & Termination Temperature Articles: NEC 310.15 / 16 / 17
- Ampacity Rating Tables:
- Table 310.16 for conductors in raceways, cables, or direct burial
- Table 310.17 for single conductors in free air
- Temperature Correction Factors:
- Table 310.15(B)(1)
- Adjustment Factors for Multiple Conductors:
- Table 310.15(C)(1)
Walkthrough for a NEC Electrical Exam Conductor Sizing Question
Question:
What is the max ampacity of a size 4 AWG THW copper conductor with termination temperature of 60°C when installed in a conduit with three other current-carrying conductors of the same size and insulation, and in a location with an ambient temperature of 98°F?
Step 1: Determine Conductor Temperature Rating
- The termination temperature is given as 60°C.
- THW insulation is rated for 75°C, but we must use the lower of the conductor rating or termination temperature.
- Therefore, we will use the 60°C column in Table 310.16.
Step 2: Identify Installation Method & Ampacity
- The conductor is installed in a conduit.
- We will use Table 310.16 for conductors in raceways.
- Base ampacity from Table 310.16 for 4 AWG copper at 60°C: 70 A
Step 3: Apply Temperature Correction Factors
- The ambient temperature is 98°F, which exceeds 86°F, so we need to apply a correction factor.
- From Table 310.15(B)(1), for 98°F and a 60°C rated conductor, the correction factor is 0.82.
Step 4: Apply Adjustment Factors
- There are four current-carrying conductors in the conduit.
- From Table 310.15(C)(1), for 4-6 current-carrying conductors, the adjustment factor is 0.80.
Calculation
- Base ampacity from Table 310.16 for 4 AWG copper at 60°C: 70 A
- Apply temperature correction factor: 70 A × 0.82 = 61.6 A
- Apply adjustment factor for number of conductors: 61.6 A × 0.80 = 45.92 A