Transformer conductor sizing questions are common on electrical licensing exams because they test multiple concepts: load calculations, continuous load factors, and conductor ampacity selection. Understanding how to handle different transformer configurations (single-phase, three-phase, and multiple transformers) is crucial for passing your exam.
Example Transformer Conductor Sizing Questions on NEC Electrical Exams
- What's the smallest permissible size of THWN copper conductor to feed a 3Ø transformer bank (three 30 kVA, 480-120/240 V single-phase transformers) from a circuit breaker?
- A 225 kVA, dry-type, 480-208/120 V transformer's primary side must be fed with a minimum __________ THW copper conductor. Transformer terminations are rated at 167°F.
- An office building uses a 75 kVA, 3-phase, 600-208Y/120 V transformer terminating at 167°F (75°C). The secondary side wiring requires a minimum __________ RHW copper conductor.
How to Identify a Transformer Conductor Sizing Question on NEC Electrical Exams
Key phrases to look out for:
- "Transformer primary/secondary conductors"
- "Minimum conductor size"
- "Full load current"
- "kVA rating"
- "Transformer bank"
- References to Article 450
- Temperature ratings
When you spot these elements:
- Identify transformer configuration (single-phase, three-phase, or bank)
- Note the kVA rating(s)
- Check voltage ratings
- Refer to NEC Articles 450 and 310.16
Transformer Conductor Sizing Articles: NEC 450 and 310.16
To correctly size transformer conductors, focus on these main elements:
- Basic Calculations:some text
- Single-phase: I = VA ÷ V
- Three-phase: I = VA ÷ (√3 × V)
- Apply 125% for continuous loads
- Configuration Considerations:some text
- Individual transformers vs. transformer banks
- Primary vs. secondary conductors
- Temperature ratings and derating factors
- Special Requirements:some text
- Overcurrent protection
- Transformer termination temperature ratings
- Ambient temperature corrections
Different Transformer Configurations and Their Calculations
Single-Phase Transformers
- Formula: I = VA ÷ V
- Example: 50 kVA, 480V primarysome text
- I = 50,000 ÷ 480 = 104.17A
- With 125%: 104.17 × 1.25 = 130.21A
Three-Phase Transformers
- Formula: I = VA ÷ (√3 × V)
- Example: 75 kVA, 480V primarysome text
- I = 75,000 ÷ (1.732 × 480) = 90.32A
- With 125%: 90.32 × 1.25 = 112.9A
Multiple Transformer Banks
- Calculate total kVA first
- Example: Three 25 kVA transformerssome text
- Total kVA = 3 × 25 = 75 kVA
- Then use appropriate formula based on configuration
Key Differences Between Primary and Secondary Calculations:
- Voltage: Use the specific voltage for the side you're calculatingsome text
- Primary: Higher voltage (600V in this case)
- Secondary: Lower voltage (208V in this case)
- Current: Inversely proportional to voltagesome text
- Higher voltage = Lower current
- Lower voltage = Higher current
- Conductor Size: Usually larger on secondary side due to higher currentsome text
- Primary: Smaller conductor size typically needed
- Secondary: Larger conductor size typically needed
Walkthrough for NEC Electrical Exam Transformer Questions
Three-Phase Bank Question
Question: What's the smallest permissible size of THWN copper conductor to feed a 3Ø transformer bank (three 30 kVA, 480-120/240 V single-phase transformers) from a circuit breaker?
Step 1: Calculate Total kVA and Full Load Current
- Total kVA = 3 × 30 kVA = 90 kVA
- Primary voltage = 480V three-phase
- I = 90,000 ÷ (√3 × 480)
- I = 90,000 ÷ 831.4
- I = 108.38 amperes
Step 2: Apply 125% for Continuous Load (210.19(A))
- Minimum ampacity = 108.38 × 1.25
- Minimum ampacity = 135.47 amperes
Step 3: Select Conductor Size
- Use Table 310.16 for THWN copper at 75°C
- Need ampacity > 135.47A
- 1/0 AWG is rated 150A
- This is the smallest size that meets requirements
The minimum conductor size required is 1/0 AWG copper.
Single Three-Phase Transformer Question
Question: A 225 kVA, dry-type, 480-208/120 V transformer's primary side must be fed with a minimum __________ THW copper conductor. Transformer terminations are rated at 167°F.
Step 1: Calculate Full Load Current
- kVA = 225
- Primary voltage = 480V three-phase
- I = 225,000 ÷ (√3 × 480)
- I = 225,000 ÷ 831.4
- I = 270.95 amperes
Step 2: Apply 125% for Continuous Load (210.19(A))
- Minimum ampacity = 270.95 × 1.25
- Minimum ampacity = 338.69 amperes
Step 3: Select Conductor Size
- Use Table 310.16 for THW copper
- Need ampacity > 338.69A
- 500 kcmil is rated 380A
- This is the smallest size that meets requirements
The minimum conductor size required is 500 kcmil copper.
Secondary Conductor Sizing Question
Question: An office building uses a 75 kVA, 3-phase, 600-208Y/120 V transformer terminating at 167°F (75°C). The secondary side wiring requires a minimum __________ RHW copper conductor.
Step 1: Calculate Full Load Current for Secondary Side
- kVA = 75
- Secondary voltage = 208V three-phase
- I = 75,000 ÷ (√3 × 208)
- I = 75,000 ÷ 360.18
- I = 208.42 amperes
Step 2: Apply 125% for Continuous Load (210.19(A))
- Minimum ampacity = 208.42 × 1.25
- Minimum ampacity = 260.53 amperes
Step 3: Select Conductor Size
- Use Table 310.16 for RHW copper at 75°C
- Need ampacity > 260.53A
- 300 kcmil is rated 285A
- This is the smallest size that meets requirements
The minimum conductor size required is 300 kcmil copper.